DOI of the published article https://doi.org/10.1016/j.geothermics.2024.102912
Exploiting heat gains along horizontal connection pipes in existing borehole heat exchanger fields
DOI:
https://doi.org/10.31224/3360Keywords:
borehole heat exchanger, horizontal connection pipe, header pipe, heat loss, heat gain, optimised operationAbstract
This study investigates three options for utilising the additional capacity of borehole heat exchanger (BHE) fields through gains along horizontal connection pipes, whose contribution is routinely ignored. The analysis considered thermal load profiles with different heating to cooling ratios and finds that the effect of horizontal pipes becomes more significant with unbalanced loads. The study explores the potential of extended operation, increased loads and an optimised operating strategy to exploit the idle capacity gain from the horizontal connection pipes. It is shown that for the scenarios investigated, the BHE field operational time can be extended by more than 25 years without violating the critical fluid temperatures in the design phase. Alternatively, the thermal load can be increased by up to 26 %. In addition, the study highlights the potential of an optimised operating strategy involving adjustments to the number of BHEs operated to reduce power consumption and therefore reducing operating costs in existing systems by utilising heat gains from the horizontal connection pipes.
Downloads
Downloads
Posted
License
Copyright (c) 2023 Stephan Dueber, Raul Fuentes, Guillermo Narsilio

This work is licensed under a Creative Commons Attribution 4.0 International License.