Preprint / Version 1

Air change rates in NHS general wards: weighing airborne infection risk against the energy, cost and carbon of ventilation

##article.authors##

DOI:

https://doi.org/10.31224/8762

Keywords:

hospital, ventilation, air change rate, Wells-Riley model, airborne infection, energy, carbon emissions, HEPA air cleaner, HTM 03-01

Abstract

Health Technical Memorandum 03-01 sets a design rate of six air changes per hour (ACH) for general wards in England, but the infection-control benefit and the operating cost of that rate are rarely set side by side. This study combines a Wells-Riley airborne infection model with an annual energy, cost and carbon model for a four-bed ward bay of 172.8 m³, using current UK energy prices and 2026 carbon factors. For a single infectious patient over 24 hours, modelled infection probability for each susceptible patient fell from 8.3% to 5.2% for tuberculosis and from 6.2% to 3.9% for SARS-CoV-2 when ventilation rose from 6 to 10 ACH. Each additional air change cost about £263 and 318 kgCO2e a year with a run-around coil and gas heating, and the benefit of each extra air change fell steadily as the rate rose. Reaching 10 equivalent air changes with a portable HEPA unit instead of extra outdoor air cut the added running cost by 80–89% and the added emissions by 90–95%. If an existing air handling unit is simply run faster, the added cost rises to about £4,700 a year because fan power grows with the cube of airflow. The results support keeping the HTM baseline for outdoor air and using air cleaning to go beyond it.

Downloads

Download data is not yet available.

Downloads

Posted

2026-11-08