Cooling Consequences of Scheduled Ventilation Under Visitor Timing Uncertainty
DOI:
https://doi.org/10.31224/8824Keywords:
indoor ventilation, Cooling, carbon dioxideAbstract
Comparing a scheduled ventilation strategy with a fixed constant-flow baseline can confuse a scheduling benefit with the choice of capacity. We examine whether midday outdoor-air reductions retain a cooling advantage when constant and timed policies are sized using the same carbon dioxide criterion. A drawing-informed Nanning office prototype was varied across three floor areas and three visitor durations. Four policies were sized with a common periodic mass-balance rule and tested at three visitor arrival times, giving 108 annual EnergyPlus scenarios. In the nominal 18.6725 m2 office with a 60-minute visitor, the constant policy required 12.50 L/s, whereas a two-hour half-flow policy required 19.75 L/s. The latter increased worst-profile annual ideal cooling by 7.37%. Across the nine area-duration cells, the three timed policies required more outdoor-air volume and cooling than their matched constant alternatives. A separately sized, assured-lunch-absence control reversed the result, with the two-hour half-flow policy reducing cooling by 1.05%. Numerical verification retained an unsuccessful coarse-step benchmark: the default 10-minute solver differed from exact transient end states by 28.29 ppm against a preset 25 ppm tolerance. The analytical algorithm matched the independent solution, and fine-step annual diagnostics exposed two short native reports above the research reference. The study provides a bounded comparison of capacity, schedule and visitor assumptions rather than a new control algorithm, a global optimum or a field-validated design. Cooling is thermal demand, not electricity.
Downloads
Downloads
Posted
License
Copyright (c) 2026 Xin Liang

This work is licensed under a Creative Commons Attribution 4.0 International License.