Never fully dark: presence-controlled LED lighting with a safe background level for plantrooms and rooftop plant, evaluated with UK data from 2022 to 2026

##article.authors##

DOI:

https://doi.org/10.31224/8848

Keywords:

lighting controls, presence detection, plantroom, rooftop plant, LED retrofit, energy, carbon, slips trips and falls

Abstract

Plantrooms and rooftop plant areas are visited for a few hours a week, yet their lighting is usually either left on permanently or switched off, so that staff enter dark spaces where slips, trips and falls are likely. This paper examines presence-controlled LED lighting that never switches fully off but dims to a background level chosen to keep the 20 lx average that HSE guidance gives for the movement of people. A lumen-method design for a 150 m² reference plantroom and an annual energy model were built in a spreadsheet and priced with UK electricity prices and carbon factors for 2022 to 2026. With 5 hours of occupancy a week, the proposed control used 783 kWh a year, 88% less than always-on twin T8 fluorescent lighting and 71% less than always-on LED. Keeping the room at a 20% background level cost 659 kWh a year more than switching off. The annual saving against fluorescent lighting rose from £1,167 in 2022 to £1,371 in 2026, while the carbon saving fell by 32% as the grid decarbonised. For battery luminaires on roofs, sensor standby power rather than light dominated the energy budget.