Design, Experimental Validation, and Numerical Coolant Comparison of a Compact Plate-Fin-and-Tube Rear Door Heat Exchanger with Al2O3 Nanofluid for Data Center Cooling
DOI:
https://doi.org/10.31224/8886Keywords:
Rear door heat exchanger, Plate-fin-and-tube, CFD calibration, Data center cooling, Al2O3 nanofluid, GT-SUITE, ANSYS Fluent, Computational fluid dynamics, Heat exchanger design, Experimental validation, Prototype fabrication, Liquid cooling, Thermal management, Pressure dropAbstract
Rear door heat exchangers let an air-cooled rack reject heat to water without changes to the servers. This paper describes the design and rating of a hand-built plate-fin-and-tube door exchanger sized for 5 kW inside a 100 mm door depth. The 438-fin, two-row, two-pass core has a 50 mm longitudinal pitch, outside the stated range of the air-side correlation used to rate it. CFD of an air-side unit cell and of the water circuit was used to calibrate the air-side pressure drop model and the water-side coefficient, and a GT-SUITE rack model checked the design point and the response to a measured GPU load. The calibrated model predicts 5507 W at an air-side pressure drop of 15.4 Pa and agrees within 6.8% with a low-load bench test. Al2O3 nanofluid at 1 to 4% by volume gave no useful gain at equal pumping power.
Downloads
Downloads
Posted
License
Copyright (c) 2026 Anindya Guha, Fatin Ishraque, Mohammad Sifat Hasan, Parag Mollick, Md. Sabbir Hossain

This work is licensed under a Creative Commons Attribution 4.0 International License.